United States · IEEE 1584.1 scope · PE stamped

Arc flash study services

Scope it properly. Compare the quotes properly. Award once.

Most arc flash tenders are lost or overspent before a vendor is chosen, because the scope was written loosely and the quotes were never comparable. This page is the buyer’s side of that problem: what a compliant scope must contain, what actually drives the price, who is qualified to sign, and the four checks to run on any report before you award.

What drives the cost
Field installation Engineer in arc rated coverall, hard hat, face shield and insulating gloves operating a labelled switchgear panel
Arc rated PPE selected against the calculated incident energy at that working position. The label on the door is the output of the study you are buying.
1,000+Power system studies
12Years · since 2014
21Countries
50+Fortune 500 sites
Step 1Write a scope that gets comparable bids Step 2Understand what moves the price Step 3Check who is qualified to sign Step 4Compare the reports, then award

Step 1 · the scope of work

What an arc flash study scope of work must contain

There is a standard for this, and most tenders do not cite it. IEEE 1584.1 is the guide for specifying the scope and deliverable requirements of an arc flash hazard calculation study. A scope written against it produces bids you can actually compare.

A loose scope is the single most expensive thing in this process. It does not save money at tender stage; it moves the money to a variation later, after you have already awarded and have no leverage. Nine things decide whether a bid is comparable.

  1. The equipment threshold. IEEE 1584.1 guidance is that all equipment at 208 volts three phase and above is included. State it, and state any exclusion in writing rather than leaving it to interpretation.
  2. The bus count, or how it will be established. If you know it, publish it. If you do not, say that the vendor must derive it from the single line diagram and declare it in the bid. Without this, no two prices mean the same thing.
  3. The calculation standard. IEEE 1584-2018. Name it, because the retired 2002 method produces different answers and some bids still use it.
  4. The data collection method. Who walks the plant, whether nameplates are photographed, whether trip unit settings are read at the relay, and who escorts. This is where scope quietly expands.
  5. The single line diagram basis. State whether a current SLD exists and will be issued, or whether it must be reconstructed from the field. This is the largest cost variable on a brownfield site and it belongs in the tender, not the variation.
  6. The utility fault data. Say who obtains the available fault current at the service. If nobody does, the study runs on a conservative assumption and every downstream result is inflated.
  7. The label format and quantity. NFPA 70E format, the data fields required, material, and whether installation is in scope. Printing and installing are separable and should be priced separately.
  8. The deliverable list. Incident energy report, reconciled SLD, short circuit and coordination results, label files, executive summary and action register. Anything unstated will be omitted.
  9. The acceptance criteria. Who reviews, against what, and what constitutes completion. Include the requirement for a named signature and a conformance matrix at the front of the report.

The standards a scope should name

Name them explicitly rather than referring to applicable codes. Four documents carry the weight, and a bidder who cannot say which clause governs which deliverable has not read them.

DocumentWhat it governs in your scope
NFPA 70EWork practice. The risk assessment procedure, approach boundaries, PPE selection, energised work permits, label content and the review interval.
IEEE 1584-2018The calculation. Arcing current, incident energy at the working distance, arc flash boundary. The 2002 method is retired.
IEEE 1584.1The scope itself. Specification of scope and deliverable requirements, including the equipment threshold.
NFPA 70BEquipment maintenance. Relevant because the condition of a protective device decides whether it clears in the time your calculation assumed. NFPA 70B compliance and arc flash results are connected, and a thorough auditor asks about both.

Together with OSHA 29 CFR 1910 these are the IEEE electrical safety standards and consensus documents a US arc flash tender is written against. Cite them by name in the scope and the bids you receive will be comparable.

Not sure which clauses your scope has to cite? Send it over and we will mark it up.

Send us your draft scope before it goes out. We will mark it against IEEE 1584.1 and return it, whether or not you invite us to bid. A clear scope produces comparable bids, and comparable bids are how a competent vendor wins.

Step 2 · cost

What drives the price, and why quotes differ so much

The label count is the unit. One label per assessed bus or panel. That count is established from your single line diagram before a quote exists, and it drives everything else in the estimate.

Two quotes for the same plant can differ by a wide margin simply because one counted 180 buses and the other counted 310, and neither said so. Ask every vendor for their bus count before you compare a single figure. If they cannot give you one, they have not scoped your plant.

What moves the count

The four things that become a variation after award

All four are visible during scoping if anyone asks. We ask, and we put the answers in the proposal so the basis of the number is on the page. Tell us your plant voltage and site count and a Chartered Engineer will come back with the scoped bus count.

How to perform an arc flash study · the method your scope is buying

Six steps, in this order. A bid that cannot describe them is bidding on software output.

  1. Field walkdown and data collection. Nameplates, CT and PT ratios, trip unit settings, cable runs, photographed and logged per equipment item.
  2. Single line diagram reconciliation. Drift against the as installed plant logged and co-signed before any model is built.
  3. System modelling and short circuit calculation. Bolted fault current at every bus, from verified source impedance and utility data.
  4. Protective device coordination. Clearing time at each device · the largest single lever on the result.
  5. Incident energy calculation to IEEE 1584-2018. Energy at each working position, arc flash boundary, approach boundaries and PPE category.
  6. Labels, report and handover. Print ready NFPA 70E labels, the signed report with a conformance matrix, and a workforce briefing.

Ask how we would sequence these six steps around your outage window.

Step 3 · qualification

Who can perform an arc flash analysis

An engineer competent in power system analysis, not a testing technician. Ask three things before you award: who signs each section by name, whether the single line diagram is co-signed against the as installed plant, and whether the report is PE stamped.

This matters because the calculation is the easy part. Any competent user can drive the software. What separates a defensible study from a decorative one is whether the inputs were verified, whether the assumptions were declared, and whether a named engineer is accountable for both.

The pattern to watch for is an assumptions register that disclaims the as-built drawings and then proceeds anyway. That produces a result which is precise, wrong, believed, and hanging on the wall.

Two engineers reviewing single line diagrams at a table in front of labelled motor control centre panels during a plant walkdown
The reconciliation, not the software. Drawings checked against the installed plant panel by panel, drift logged per equipment item, and the reconciled diagram co-signed by your engineer before any model is built.

Our position. The study is delivered PE stamped. Every section additionally carries a named Chartered Engineer signature: the Practice Lead drafts, the Principal Reviewer independently cross checks. We are engineers, not equipment vendors, and we do not sell the PPE we recommend.

Ask who would sign your study, by name, before you shortlist.

Step 4 · comparison

How to choose an arc flash study company

Compare the bus count first, because that is the scope. Then apply four checks to a sample report from each bidder. You can do all four in under an hour, and they will separate the arc flash study companies bidding on engineering from those bidding on software output.

CheckWhat to look for
Who signed itA named engineer on every section, not a stamp on the cover. Ask who drafted and who independently reviewed. One signature on a 200 page document is a formality, not accountability.
Were the inputs verifiedThe single line diagram co-signed against the as installed plant, nameplates photographed, CT and PT ratios confirmed, trip unit settings recorded.
Are the assumptions declaredEvery conservatism stated so an auditor can trace each number to its source. Where utility data was unavailable, the estimate should be named as an estimate.
Is it audit readyA conformance matrix at the front mapping each section to the standard it satisfies. An auditor should verify compliance in minutes rather than hunt through appendices.

Holding two or three reports already? Send them and we will run these four checks for you.

What you should be receiving

Incident energy report

Every working position under IEEE 1584-2018, with boundaries and PPE category per bus. Hand verified at critical buses.

NFPA 70E labels

Print ready, in NFPA 70E format · incident energy, boundaries, PPE category, equipment identifier, study date.

Reconciled single line diagram

Verified against the as installed plant by supervised walkdown, drift logged, co-signed by your engineer.

Short circuit and coordination study

The fault duty and clearing times the incident energy result stands on, as its own reviewable section.

Field data pack

Nameplates, CT and PT ratios, trip unit settings, cable runs. The basis of design archive that survives staff turnover.

Executive summary and action register

Two pages for EHS sign off, actions ranked by priority and assigned by discipline. What an auditor reads first.

Full anatomy of the document, section by section, is on the arc flash report page.

Check your tender asks for all six. We will tell you what is missing.

What the numbers on the label actually mean for scope

Two labels from one engagement, printed from one calculation. Reading them side by side is the fastest way to see why bus count alone does not tell you the whole story.

Low incident energy Arc flash and shock risk warning label reading 2.8 cal per square centimetre at 36 inches with a 68 inch arc flash boundary, installed on a switchgear feeder panel
2.8 cal/cm² at the stated working distance · a 68 inch arc flash boundary. A routine PPE category, and a task that can be planned normally.
High incident energy Arc flash and shock risk warning label reading 35 cal per square centimetre at 36 inches with a 1151 inch arc flash boundary, installed on a transformer panel
35 cal/cm² · a 1,151 inch boundary, roughly 96 feet. Same plant, same study. This is the result that changes how a plant is operated, not just what a worker wears.

The difference is not the standard and not the software. It is the fault duty and the clearing time at that bus, which is why the coordination study belongs inside the same scope. Halve the clearing time and you roughly halve the incident energy, which is an engineering recommendation rather than a procurement one, and it is what a good report leads with. The arc flash boundary itself is the distance at which incident energy falls to 1.2 cal/cm², the onset of a second degree burn on bare skin. The limited approach boundary and the restricted approach boundary are different things again · shock boundaries set by system voltage rather than by incident energy · and all three are routinely confused on site. Your scope should require all three to appear on every label. The underlying method, the formula and a worked calculation example are covered on arc flash hazards.

DC systems are a separate scope line. Battery rooms, UPS strings and 800Vdc data centre plant are not covered by the AC equations and need a DC incident energy calculation, with UL listed switching equipment for the duty. Put it in the tender explicitly · see DC arc flash study.

Before you tender

If you are still deciding whether you need one

OSHA does not name an arc flash study. It requires the employer to assess the hazard, determine the protection needed and provide it. An incident energy analysis is how that duty is discharged, and NFPA 70E is the consensus standard recognised for the method.

Because the duty is written as an outcome rather than a prescribed method, an employer who has performed no assessment has nothing to point to. The same architecture applies to fire risk assessment and machine guarding. And the interval is not open-ended: the arc flash risk assessment is reviewed at intervals not exceeding five years, and sooner on any major modification or renovation.

1 · Incident

An arc fault injures a worker during routine switching.

2 · Investigation

The regulator, your insurer and counsel ask for the hazard assessment.

3 · No current study

Outdated labels, unverified data, lapsed training records.

4 · Liability

Citation, penalties, coverage disputes, personal exposure for the responsible manager.

In practice the tender is triggered by a citation or inspection finding, an incident investigation, an insurer requirement at renewal, a corporate EHS standard, commissioning of new plant, or the five year review falling due. The recurring side of that · label currency, training cycles and the five year re-study · is handled as a programme rather than a repeat purchase. That is VB Arc360.

Not sure whether you are due? Tell us the date on your existing labels.

Where we work, and how long it takes

VB Engineering runs a United States entity with the team in Houston and Katy, Texas, supported by the analytical bench in Hyderabad. Field work, label installation and handover briefings run from the US side; modelling runs across time zones, which is why a study that would take eight weeks sequentially completes in six.

Six weeks end to end for a typical industrial site, eight for a multi substation facility. Walkdown two to three days on site, SLD reconciliation about a week, modelling and calculation two to three weeks, label production and installation two weeks. No plant shutdown is required for the analysis · only label installation needs brief access to each item, sequenced around your outage window.

Regions, sectors and site coverage are set out on the United States page.

Ask for a delivery window against your planned outage.

The studies inside the same scope

Questions buyers ask before awarding

Who can perform an arc flash analysis?

An engineer competent in power system analysis, not a testing technician. Ask three things before you award: who signs each section by name, whether the single line diagram is co-signed against the as installed plant, and whether the report is PE stamped. VB Engineering delivers all three as standard.

What does an arc flash study cost?

An arc flash study is priced against the label count, one label per assessed bus or panel. That count is established from your single line diagram before any quote exists. Ask every vendor for their bus count before you compare a single figure. We scope the count first and price against it.

What should an arc flash study scope of work include?

IEEE 1584.1 is the guide for specifying arc flash study scope and deliverables. A sound scope names the equipment threshold, the data collection method, the calculation standard, the label format, the deliverable list and the acceptance criteria. We write scopes to IEEE 1584.1 and will review yours.

What equipment must be included in an arc flash study?

IEEE 1584.1 guidance is that all equipment at 208 volts three phase and above should be included. In practice the boundary is set by where energised work can occur, so motor control centres, switchboards, panelboards, transformers and switchgear are all in scope unless a written exclusion is agreed.

How should I compare arc flash study quotes?

Compare the bus count first, because two quotes for the same plant can differ entirely on scope. Then check four things in a sample report: a named engineer signing every section, field verified inputs with a co-signed single line diagram, every conservatism declared, and a conformance matrix at the front.

Is an arc flash study required by OSHA?

OSHA does not name an arc flash study. It requires the employer to assess the hazard, determine the protection needed and provide it. An incident energy analysis is how that duty is discharged, and NFPA 70E is the consensus standard recognised for the method. VB Engineering delivers that analysis PE stamped.

Is arc flash analysis required by OSHA?

The same answer applies, and the wording is worth settling because tenders use both terms. OSHA requires the hazard to be assessed and the protection provided; it does not prescribe the method. An arc flash analysis performed to NFPA 70E and IEEE 1584-2018 is how that duty is evidenced.

How long does an arc flash study take?

Six weeks end to end for a typical industrial site, eight for a multi substation facility. Walkdown two to three days on site, single line diagram reconciliation one week, modelling and calculation two to three weeks, label production and installation two weeks. No plant shutdown is required for the analysis.

Is the arc flash study report PE stamped?

Yes. The study is delivered PE stamped, and every section additionally carries a named Chartered Engineer signature. The Practice Lead drafts, the Principal Reviewer independently cross checks, and the deliverable is structured for OSHA inspection, insurer review and the procurement file.

Proof of delivery

What the scope buys you, on the plant floor

A study that ends at a PDF has not changed anything. Every engagement finishes with labels on the equipment, boundaries marked where the calculation demands them, and a handover briefing so the workforce understands the labels before energised work resumes. Specify those three in your scope and you will get them.

Warning arc flash and shock hazard label installed on an equipment panel showing incident energy, flash hazard boundary, limited and restricted approach distances
LabelsIncident energy, arc flash boundary, limited and restricted approach, PPE category and equipment identifier. Installed and witness signed.
Yellow arc flash boundary line marked on the floor in front of an electrical panel lineup
BoundariesMarked at the equipment where the calculated distance requires a physical demarcation, in the same visit as the labels.
Motor control centre cubicle bank with an arc flash warning label on every door alongside the rotary isolator handles
At scaleEvery door, not a sample. A study is finished when the label a worker reads before opening a panel is on all of them.

Selected clients · 1,000+ studies · 21 countries

Bayer Pfizer TATA Adani JSW Nestle Rolls-Royce DuPont Siemens Amazon Bosch Coca-Cola Hindalco Kia Mahindra ITC Bayer Pfizer TATA Adani JSW Nestle Rolls-Royce DuPont Siemens Amazon Bosch Coca-Cola Hindalco Kia Mahindra ITC

Get your scope and bus count reviewed

Send your draft scope of work, or just your plant voltage, substation count and sites. A Chartered Engineer responds inside 24 hours with the scoped bus count and a marked-up scope against IEEE 1584.1 · whether or not you invite us to bid.

  • Four fields. No phone interview to start.
  • Routes directly to the Power System Studies Practice Lead.
  • Houston and Katy, Texas · US delivery team.
  • Every deliverable PE stamped and Chartered Engineer signed.

Arc flash warning label installed and witness signed on an equipment panel
The end state your scope is buying: a label on every assessed panel, carrying the number a worker reads before opening it.

Scoping an arc flash study? We will review your scope of work against IEEE 1584.1 and return a bus count.